Backflow test report, water system copy
Aug 20, 2026
Record
Company
Sample company (fictional)
Trade
Backflow Testing
Test
Aug 20, 2026
Property owner
Name
Cedar Row Properties
Email
jordan@example.com
Phone
555-0111
Address
137 Linden Ave, Springfield
Property
Name
Jordan Pike
Address
137 Linden Ave, Springfield
Location
44.050999999999995, -123.09100000000001
Assembly
Serial number
SE-4137
Type
RPDA (reduced pressure detector)
Location on the property
Loading dock
Size
8.25 in
Manufacturer
Tollin Industrial
Model
MO-4137
State
Washington
Hazard served
Hazard served 2
Hazard level
Non-health or low hazard
Protection
In-premises (a fixture or system)
Service connection
Non-residential
Install date
Aug 18, 2026
Installation
New
Serial number of the assembly it replaced
RE-4137
Water system
Water system 2
Water system ID
Water system ID 2
On a fire line
No
On a non-potable supply
No
Detector bypass: make and model
BY-4137
Detector bypass: serial number
BY-4137
Detector bypass: size
2.75 in
Test
Test date
Aug 20, 2026
Reason for the test
New installation
Result
Failed
Tester
Jordan Pike
Licence or certificate number
TE-4137
Test kit serial number
KI-4137
State
Washington
Licence or certificate expires
Sep 4, 2026
Tester phone
555-0111
Test kit make and model
KI-4137
Test kit last accuracy check
Feb 19, 2026
Gauge kept for
Non-potable water
Sent to the water system on
Aug 20, 2026
Sent through
Email
Owner copy sent on
Aug 20, 2026
Installation
Make and model is an approved assembly for this use
Pass
Installed in the orientation its approval allows
Fail
Installed as the manufacturer and the local code require
Pass
RP and RPDA: an air gap below the relief valve discharge
Pass
Test cocks and shutoff valves present and working
Pass
Reachable for testing and repair
Pass
Assembly type suits the hazard it protects
Pass
Readings
Reading
Value
Result
RP, RPDA: first check held at Washington DOH memo to certified testers: USC Tenth Edition field test procedures (2011) (https://doh.wa.gov/sites/default/files/legacy/Documents/4200/bats.pdf), checked 2026-10-28
8 psid
Pass
RP, RPDA: relief valve opened at Washington DOH memo to certified testers: USC Tenth Edition field test procedures (2011) (https://doh.wa.gov/sites/default/files/legacy/Documents/4200/bats.pdf), checked 2026-10-28
3.8 psid
Pass
RP, RPDA: relief valve Washington DOH memo to certified testers: USC Tenth Edition field test procedures (2011) (https://doh.wa.gov/sites/default/files/legacy/Documents/4200/bats.pdf), checked 2026-10-28
Opened
Pass
First check valve
Closed tight
Recorded
Second check valve
Closed tight
Recorded
DC, DCDA: first check held at
Not taken
Recorded
DC, DCDA: second check held at
Not taken
Recorded
PVB, SVB: air inlet opened at
Not taken
Recorded
PVB, SVB: air inlet
Opened fully
Recorded
PVB, SVB: check valve held at
Not taken
Recorded
Detector bypass check held at
Not taken
Recorded
Line pressure
Not taken
Recorded